METHOD OF PROTECTING A PLASTIC PIPE WITHOUT INSULATION PENETRATING A RIGID WALL ACCORDING TO ETA-17/1064
1 - rigid wall with a thickness of B ≥ 100 or 150 mm (see Annex B)
2 - plastic pipe, diameter "D" and pipe wall thickness "T" (see Annexes B and D)
3 - Piro Wrap PW with dimensions [h x s], placed in the center of the wall
4 - space between the pipe and the wall structure, width u = max.
30 mm, filled with cement mortar or mineral wool with density min. 50 kg/m3
Technical drawing 1
Steps 1 - 5
Read in the table pipe diameter and select the appropriate size of Piro Wrap PW.
Wrap around the pipe and secure the wrap with the integrated adhesive.
Slide the secured wrap into the partition. Location of the wrap inside the hole - central position along the wall axis.
Fill the space between the pipe and the partition with cement mortar.
Mark the completed penetration seal with the attached label, mark Piro Wrap PW on it, enter the date and name.