METHOD OF PROTECTING A SINGLE CABLE PENETRATING WALL AND FLOOR  ACCORDING TO ETA-17/1062

1.png

1 - flexible or rigid wall with a thickness of min. 100 mm
2 - single cable with a diameter of max. 13 mm
3 - PiroCoating with dimensions: length L = min. 300 mm, thickness
     h = min. 1.2 mm, length l1 = min. 50 mm, thickness h1 = min. 0.6 mm
4 - space between the pipe and the partition structure, max. a = 30 mm,
     filled with mineral wool with a density of min. 50 kg/m3
5 - gypsum mortar with a thickness of min. g1 = 5 mm

Technical drawing 1
1.jpg

Fill the space between the
cable and the partition tightly.
Use mineral wool with a
density of min. 50 kg/m3 or
cement mortar.

Steps 1 - 4

By using a brush, apply
PiroCoating on the partition
in such a way that a ring with
a width of min. 50 mm and a
thickness of min. 0.6 mm is
created.

2.jpg
3.jpg

Apply the PiroCoating on a
cable so that a ring with a
width of min. 300 mm and a
thickness of min. 1.2 mm is
created.

Mark the completed
penetration seal with the
label. Mark PiroCoating on it,
enter the date and the name.