METHOD OF PROTECTING A CABLE BUNDLE PENETRATING WALL AND FLOOR  ACCORDING TO ETA-17/1062

1.png

1 - flexible or rigid wall with a thickness of min. 100 mm
2 - single cable with a diameter of max. 13 mm
3 - PiroCoating with dimensions: length L = min. 300 mm, thickness
     h = min. 1.2 mm, length l1 = min. 50 mm, thickness h1 = min. 0.6 mm
4 - space between the pipe and the partition structure, max. a = 30 mm,
     filled with mineral wool with a density of min. 50 kg/m3
5 - gypsum mortar with a thickness of min. g1 = 5 mm

Technical drawing 1
1.jpg

Fill the space between the cable and the partition tightly. Use mineral wool with a density of min. 50 kg/m³ or cement mortar.

Steps 1 - 4

By using a brush, apply PiroCoating on the partition
in such a way that a ring with a width of min. 50 mm and a thickness of min. 0.6 mm is created.

2.jpg
3.jpg

Apply the PiroCoating on a cable bundle so that a ring with a width of min. 300 mm and a thickness of min. 1.2 mm is created.

Mark the completed penetration seal with the label. Mark PiroCoating on it, enter the date and the name.