PiroCoat A Bucket 3kg View without shine

Technical Approval: ETA-17/1062

Constancy of Performance: 1488-CPR-0726/W

The declaration of performance: PIRO/06-2018-09-10

Application:

 

One-component ablative mass for fireproofing mineral wool in walls and ceilings used as:

Pasta_A_rury_palne_z_multitube_w_wełnie
Pasta_A_rury_stalowe_w_wełnie__przekró
Pasta_A_przejścia_mieszane_przekrój.jp

Filling mixed penetrations

Heat-insulated metal pipes

Insulating coating for flammable pipes

For walls and ceilings made of:

BETON bez cieniapng.png
CEGŁA_bez_cienia.png
Regips bez cienia.png
Piktogram Ytong.png

CONCRETE

CERAMIC BRICKS AND AIR BRICKS

 

PLASTERBOARDS

 

SILICATE BLOCKS

 

Product description and specifications:

PiroCoat A ablation paste is intended for fire protection of mineral wool used as: covering of steel pipes passing through partitions, filling combined fireproof installation penetrations, filling gaps and expansion joints in walls and fire ceilings, fireproofing of gypsum plasterboards or filling between them. PiroCoat A is a one-component ablative paste, which is an aqueous dispersion of synthetic resin. The coating made of this mass is completely non-flammable. It is characterized by endothermic properties. In fire conditions, it blocks its spread.

  • Fire resistance class: up to EI 120

  • Reaction to fire: Bfl-s1; B-s2,d0

  • Color: creamy-white

  • Density: 1,56 ± 5% g/cm³

  • Environment class: Z1, Z2

  • Storage temperature range: from +5°C  to +30°C

  • Shelf life: 10 months in the original sealed bucket

  • Theoretical amount of mass needed (kg/m²): 1 mm thick coating 1,93 kg/m²

  • Oxygen index: ≥45

  • Package: bucket - 3 and 10 kg, cartridge 310 ml

         

 

The way of protecting  flammable pipes with mineral wool cover.

Application examples:

 
Etykieta Karton lewa 1.jpg
Etykieta Karton lewa 2.png
Etykieta Karton lewa 3.png
Etykieta Karton lewa 4.png

Put  Piro Multitube  PM on the pipe under the insulation and slide it into the wall.

Then put insulation on the pipe and a tape.

Fill the remaining space with mineral wool. By using a putty knife, apply PiroCoat A paste to form a ring with a width of min. 50 mm and thickness min. 0.6 mm.

Apply PiroCoat A paste to the pipe cover so that a ring forms with a width of min. 50 mm and thickness min. 0.6 mm.

Mark the penetration with the attached label, mark Piro Multitube PM on it, enter the date and name.

The way of protecting metal pipes in mineral wool insulation penetrating floor or wall

(protection should be done on both sides).

Etykieta Karton prawa 1.jpg
Etykieta Karton prawa 2.jpg
Etykieta Karton prawa 3.jpg
Etykieta Karton prawa 4.jpg

Fill the space between the pipe insulation and the partition tightly. Use mineral wool with a density of min. 60 kg/m³ or cement mortar.

By using a putty knife, apply PiroCoat A to the partition so that a ring with a minimum width of 50 mm and a minimum thickness of 0.6 mm is formed.

Apply PiroCoat A to the pipe cover so that a ring is formed with a minimum width of 50 mm and a minimum thickness of 0.6 mm.

Mark the penetration with the attached label, mark PiroCoat A on it, enter the date and name.

The way of protecting the combined penetrations of pipes and cables in floors and fire ceilings

(protection should be done on both sides).

Etykieta_Karton_tył_1.jpg
Etykieta_Karton_tył_2.jpg
Etykieta_Karton_tył_3.jpg
Etykieta_Karton_tył_4.jpg

Fill the hole in the wall from two sides with mineral wool boards with a minimum density of 150 kg/m³ and a minimum thickness of 50 mm.

By using a putty knife apply a 1.2 mm layer of PiroCoat A onto the wool.

Protect pipes and cables according to the instructions in the catalog.

Mark the penetration with the attached label, mark all Pirosystem materials used on it, enter the date and name.