Piro Collar PC L 110
>> PRODUCTS >> COLLARS >> PIRO COLLAR PC L 110 >> APPLICATION >> PRODUCT DESCRIPTION AND SPECIFICATIONS

Technical Approval: ETA-17/1063
Constancy of Performance: 1488-CPR-0725/W
The declaration of performance: PIRO/08-2018-09-10
Application:
A set of fire protective collars for protecting pipes and cables penetrating fire walls and ceilings




Single flammable pipes: PVC, PE, PEHD, PP without insulation in walls and ceilings
Single non-flammable pipes: steel, copper, iron, insulated with foamed rubber in walls and ceilings
Single flammable pipes: PVC, PE, PEHD, PP insulated with PE foam in walls and ceilings
Non-flammable pipes insulated with foamed rubber in sets with a cable in the walls and ceilings
Flammable pipes: PVC, PE, PEHD, PP and non-flammable: copper, steel and cast iron in mixed penetrations





Possibility to mount larger collar diameter on pipe socket or outlet
Possibility to mount a "U-shaped" collar on the pipe elbow at a short distance from the wall or ceiling
Possibility to mount a larger size of collar on a pipe penetrating wall or ceiling at an angle
Possibility to mount 2/3 of the collar on a pipe running very close to the corner
Possibility to mount collars with zero distance between pipes

For walls and ceilings made of:



CONCRETE
CERAMIC BRICKS
AND AIR BRICKS

SILICATE BLOCKS
PLASTERBOARDS
Product description and specifications:
Piro Collar PC L is an ideal solution for protecting penetrations through walls or ceilings, where flammable pipes or non-flammable pipes pass and they are insulated with synthetic insulation foam type FEF. It can also be used for cable bundles. The set consists of elements that allow to build a collar of any diameter in the range from 25 mm up to 110 mm.
The set provides a solution for all types of pipes and cables
in walls and ceilings made of various materials.
-
Fire resistance class: up to EI 120 U/C, C/C, C/U
-
Reaction to fire: B-s2, d0
-
Environment class: Z1, Z2
-
Storage temperature range: from +5°C to +30°C
-
Shelf life: no limit, the recommended period is not longer than 24 months
-
Package: 1 set
The set consists of:

Segment cover
2 m

Intumescent insert
2 m

Mounting brackets
Mounting dowels